Vacuum fire protection technology

The VACTEC Sprinkler® Vacuum System is a complete FM-approved fire protection technology offering outstanding features and benefits such as corrosion inhibition and the use of mesh-type piping networks. A versatile and durable solution, the system can operate with any available water source, including wastewater, industrial water, river water, rainwater and seawater.

Fully tested and ready for connection to the water supply and sprinkler piping network, the system includes control valves, vacuum pump, control panel and vacuum controller.

These vacuum fire protection systems are available in automatic or pre-action configurations (without, single or double interlock).

Available sizes

Dimensions*Empty weight
Vacuum unitFeeder
∅A
Riser
∅B
Drain manifold
∅C
Length
L
Width
W
Height
H
DN80
(3")
DN80
(3")
DN80
(3")
DN50
(2")
1168mm
(46")
635mm
(25")
1956mm
(77")
412 kg
(908.3 lbs)
DN100
(4")
DN100
(4")
DN100
(4")
DN50
(2")
1168mm
(46")
635mm
(25")
1956mm
(77")
460 kg
(1014.1 lbs)
DN150
(6")
DN150
(6")
DN150
(6")
DN50
(2")
1168mm
(46")
635mm
(25")
1956mm
(77")
537 kg
(1183.9 lbs)
DN200
(8")
DN200
(8")
DN200
(8")
DN50
(2")
1372mm
(54")
787mm
(31")
2057mm
(81")
740 kg
(1631.4 lbs)
* precision : ± 6,4mm (1/4″)
shema

Specifications

  • Assembled, programmed and tested to ISO-9001 standards
  • Viking Model F-1 vertical outlet deluge valve
  • Stand-alone system using Viking VFR-400 control panel
  • Compact, attractive and easy to move
  • Neoprene seals on all doors to eliminate vibration
  • No open drain funnels inside the cabinet
  • Access hatch for emergency manual release valve
  • Serial number assigned to each unit for traceability
  • Standardized operation and maintenance manual

Other features & benefits

  • Inhibits corrosion by removing oxygen and moisture
  • Prevents the formation of ice plugs by automatically eliminating residual water
  • Enables the design of cost-saving mesh-type networks
  • Allows use of a roughness factor of C = 120 with black steel pipes
  • Extremely fast system start-up (<5 s)
  • Real-time monitoring of vacuum atmosphere
  • Calculation software available to estimate filling time

Vacuum controller

The vacuum pressure controller controls the vacuum pump, maintaining the vacuum level in the piping network between -180 mbar (-2.6 psi) and -150 mbar (-2.2 psi). It displays the pressure level, time and frequency of vacuum pump operation in real time, providing useful information on any changes in the pipe network.

In the event of fire, the vacuum controller detects the activation of a sprinkler head, generates an alarm and triggers the system in less than 5 seconds.

Vacuum controller
Corrosion inhibition

Corrosion inhibition

Vacuum technology inherently inhibits corrosion by removing oxygen and moisture from piping.

It offers an economical, long-term solution on applications where piping corrosion, blockages and ice plugs can affect system performance, and where maintenance problems are a concern.

The inhibiting atmosphere is created rapidly, with normal pressure reached within minutes of system activation, creating the right atmosphere to inhibit corrosion. System pressure is then monitored in real time by the controller, ensuring the required vacuum level is always maintained.

Vacuum pump

Vacuum is created using a controlled vacuum pump.

The vacuum pump can establish the required level of vacuum in the piping network in less than 4 minutes for a 3,800-liter system, saving on commissioning and maintenance time.

The vacuum pump’s advantages over an air compressor include silent operation and minimal maintenance.

pompe-_C3_A0-vide-recadre-e1517483215702-304x304
Vacuum pump
Vanne-isolement-recadre-2-304x304-1
Isolation
valve

Isolation valve

For easier maintenance, an isolation valve is installed on the riser. It also allows full-flow testing without filling the system piping. A sight glass on the main drain provides visual confirmation of water flow.

Sprinklers for vacuum system

The sprinklers used must be specifically approved for use on vacuum systems. Consult us for a list of approved sprinklers or refer to the manufacturers’ technical data sheets.

Sprinklers
Control panel

Control panel

The Viking VFR-400 panel is cULus listed, FM approved and meets the requirements of UL 864-9. The panel includes menu-driven programming for easy configuration. It is compatible with linear and point thermal fire detectors, smoke detectors, flow indicators, low and high pressure switches, and manual trigger stations.

Options for Vactec Sprinkler®units

  • Semi- or fully flanged option
    When required by the customer, the Vactec Sprinkler® unit can be fitted with semi-flanged or fully flanged connections.
  • Galvanized option
    This option includes the main manifold and the vacuum station riser in galvanized steel.

Preaction & Automation

Vacuum sprinkler systems operate in much the same way as dry-pipe sprinkler systems, but with much higher overall performance. They also enable network configurations previously reserved for wet-pipe sprinkler systems: large networks, meshed networks, looped networks, etc.

Pre-action mode operation

automatic-mode-ope

Automatic mode operation

pre-action-mode-ope